1. Program the Detection Circuit as a “Key Point”
and set the attributes as “F * * * |* A * *”. The
“F” attribute indicates that the “Full Set Group”
isselected whenthe keyswitch isswitchedfrom
“Healthy” to “Active”. The “A”attribute indicates
that “Code Set Group A” is selected when the
keyswitch is switched from Healthy to
“Shorted”.
2. Program the code set groups so that the
correct combination of wards are set and
unset. In this example the code set groups are
set as follows:
Full Set Group: [SABC]
Code Set Group A: [ AB ]
3. Program panel output 2 as “General Fault”
(044), this will provide a visual indication that
one or more circuits are in error when setting
the system.
Time Switch Application Example
This application example shows how to use “Time
Switch A” and the “Key Point circuit to set and
unset the system. The time switch will be
programmed so that panel is automatically set at
18:00 and unset at 08:00 from Monday to Friday,
and will then remain set over the weekend.
1. Program the Detection Circuit as a “Key Point”
and set the attributes as “F * * * |* * * *”. The
“F” attribute indicates that the “Full Set Group”
is selected when the circuit changes from
“Healthy” to “Active”. See “Program Circuits
and Attributes”, on page 25).
2. Program the code set groups so that all wards
are set and unset for the “Full Set Group” (see
“Code set Groups”, on page 43):
Full Set Group: [SABC]
3. Program Panel Output 1 as “Time Switch A”
(040), thisis used to switch the“keyPoint”circuit
from Healthy to Active. See Panel &
Remote Keypad Outputs”, on page 22.
4. Program “Time Switch A” as follows, see “Time
Switches”, on page 22.:
Timer 1 Timer 2 Timer 3
On Time 18:00 00:00 00:00
Off Time 08:00 00:00 00:00
Mon 4
Tue 4
Wed 4
Thu 4
Fri 4
Sat
Sun
Alarm Abort & Confirmation
Both the TS790 and TS900 support “Alarm Abort”
and “Sequential Confirmation”. The alarm abort
canbeachievedbyeithersendinganabortsignal
on a dedicated channel (normally channel 7) or
by restoring the alarm channel.
Alarm Abort Operation
When the alarm is triggered the system transmits a
Channel 3 (Alarm) to the central station. If the
system is unset within the “Abort Delay” period the
abort output is triggered and Channel 7 (Abort) is
transmitted to the central station.
Sequential Confirmation Operation
When the first alarm is triggered, the system
transmits Channel 3 (Alarm) to the central station.
If a different zone is activated the system transmits
Channel 8 (Second Alarm).
Control Panel
Panel Output 1
Panel Output 1 is programmed as:
"Time Switch A" (040)
Circuit X is programmed as:
"Keypoint" with the attributes set as:
"F*** | ****".
COM
N/C
N/O
ZX
Circuit X
TX
Figure 30 Time Switch Wiring