07 Bell Delay
This timer delays the activation of the external
bell/sounder and internal sounders. This timer
has a working range of 000-199 minutes. Note:
Any alarm during the entry procedure will
cancel the bell delay.
08 Double Knock Delay
This is the “Double Knock” time window in which
either two circuit activation must occur within
this time to generate an alarm condition. Or
the circuit must remain active for the whole
duration of this time to generate an alarm
condition. This will only apply to circuits with the
“Double Knock” attribute. This timer has a
working range of 000-199 seconds.
09 Test Time
This timer varies the number of days that “Test”
attribute may be applied to a circuit. If the
timer is set to 000 then circuits will remain on
test until the “Test” attribute is removed. This
timer has a working range of 000-030 days.
10 Second Entry
When the “Entry Timer” has expired the “2nd
Entry timer” starts to count down, if at the end of
this time the system or area has not been unset
then a full alarm will be generated. This timer
has a working range of 000-199 seconds.
11 Service Time
The installation company may use this timer to
periodically generate a “SERVICE REQUIRED”
message so that the user is reminded that a
service call is required. The users may continue
to set and unset the system. When the
engineer attends the site and enters their
passcode the message is cleared. The service
timer is re-started when the engineer re-selects
this timer option. To disable this feature set the
timer to 000. This timer has a working range of
000-199 weeks.
12 Payment Time
The installation company may use this timer to
prevent the users from setting the system.
When the timer has expired the “CALL
ENGINEER” message is displayed and the users
are unable to set the system until the engineer
has reset the system or the user has been
provided with a “Remote Reset” code. To
disable this feature set the timer to 000. This
timer has a working range of 000-199 weeks.
13 Part Set Bell Delay
This is a "Part-Set Bell Delay" and operates as
follows:
a) If the "Pset Com.Dly" is set to 000 and an
alarm is activated whilst the system is part-set,
the "Bell Delay" timer is started. At the end of the
bell delay the internal sounders are activated
for the duration of the "Pset Bel.Dly". At the end
of this delay the bell output is activated.
b) If the "Pset Com.Dly" is not set to 000 and
an alarm is activated whilst the system is
part-set, the "Bell Delay" timer is cancelled and
the internal sounders are activated for the
duration of the "Pset Bel.Dly". At the end of this
delay the bell output is activated.
If the "Part Set Bell Delay" timer is set to 199 the
bell output is not activated when an alarm
occurs whilst the system is part set. This timer
has a working range of 000 - 199 seconds.
14 Courtesy Duration
This timer is used to control the duration of the
output type “Courtesy Light”. This timer has a
working range of 000-199 seconds.
15 Access Code Duration
This timer is used to control the duration of the
output type “Access”. This timer has a working
range of 000-199 seconds.
16 Modem Rings
This counter is for use with the DC58M, it allows
the installer to specify how many rings are
required before the DC58M picks up the call. If
the counter is set to 000 it will pick the call up as
soon as any incoming ringing is detected.
Note: If the system is fitted with a DC3M, the
counter must be set to zero. This counter has a
working range of 000-199.
17 Point ID Alarms
When using the DC58 or DC58M and "Point ID
Extended Reporting". The number of point ID
alarms that are transmitted to the central
station per circuit are controlled by the value of
this counter. e.g., if the counter is set to 003
then all circuits will report 3 activation’s before
they are locked out from sending any more.
Note: this does not affect the re-arm of the
zone. This counter has a working range of 000 -
199.
28
Engineer’s Menu 1 TS790 & TS900 Installation Manual