Initial Power-Up
1. Place a small screwdriver blade between the
pins on the control panel PCB, marked
FACTORYRESTART(locatedjustbelowtheLEDs).
This will ensure the factory defaults are loaded
as shown below:
Engineer Code 1234
User Code 1 5678
Zone 1 Alarm
Zone 2 Access
Zone 3 Alarm
Zone 4 Alarm
Zone 5 Alarm
Exit Time 30 Seconds
Entry Time 30 Seconds
Bell Duration 20 Minutes
Bell Output SAB(-veapplied)
Remote Reset Number 004
Setting Mode Timed Set
Reset Authority User Reset
Number Of Rearms 3
Operation Of Keyswitch Away Set (Full)
RST- Output Detector Reset
HOME Set Configuration Zone 1 Omitted
Factory Default Settings
2. Switch on the 240V mains supply, when the
green UNSET LED is lit remove the screwdriver
blade. The internal alarm will sound and the
TAMPER LED will light.
3. Entertheengineer’spasscode(default1234),
the alarm will silence. Enter the engineers
passcode again and the TAMPER LED will flash
(engineer programming menu selected).
4. Connect the standby battery. If the TAMPER
LED lights permanently and the internal alarm
sounds when the battery is connected, then it
may be incorrectly connected or it may be
totally discharged. Disconnect the battery
immediately and reconnect or replace as
appropriate.
5. Pushthebatteryintoplaceatthebottomofthe
housing and re-fit the front cover.
On the TS410 you MUST connect the earth
bonding cable from the front cover to the
spade connection point, see figure 2.
6. Fit the battery link in the external sounder and
replace cover.
7. The system is now ready for programming.
13