Chart 1 - Zone Faults
20
Testing & Fault Finding TS400/TS410 Installation Instructions
Enter 4 digit
engineer code and
then press 3 to select
walk test mode
Relevant zone LED
on and pulsed
sounder
Remove wiring from
faulty zone and link
with a piece of wire.
Remove link from
faulty zone and re-fit
zone wiring.
Remove zone wiring
from detector and
twist together
If the control panel
sounder remains
silent, the fault is in
the detector
If the control panel
sounder is puled,
there is an open
circuit in the wiring.
No zone LED's on
and sounder is off.
Relevant zone LED
still on and pulsed
sounder.
Control Panel Faulty.
Relevant zone LED
light's and sounder
changes to a pulsed
tone.
Control panel and
detector are OK.
Enable case tamper
and re-fit cover.
No change in
control panel
indecations.
Remove the wiring
from the faulty zone.
Relevant zone led
light and sounder
changes to a pulsed
tone
Re-fit zone wiring at
control panel.
remove zone wiring
from detector
No zone LEDs on
and sounder is off.
Control Panel Faulty
If the control panel
sounder remains
silent, there is a
short in the wiring.
Activate the
relevant detector
No zone LED's on
and sounder is off.
Remove control
panel front cover
and disable the case
tamper switch
If the control panel
sounder is pulsed,
the fault is in the
detector
Permanent Zone
Fault
Detectors Fail To
Operate